dc.description.abstractNo presente trabalho foi feita a simulação computacional de três salas cirúrgicas e de alguns ambientes contíguos. Este estudo teve como objetivo verificar a influência dos diferentes layouts no conforto térmico dos ocupantes, na qualidade do ar interior, no dimensionamento dos equipamentos de climatização e no gasto energético. Todos os ambientes foram simulados para as condições climáticas de cinco capitais Brasileiras: Belém, Brasília, Porto Alegre, Recife e São Paulo. Estudou-se três tipos de distribuição arquitetônica. No Caso 1, o layout apresentado foi uma sala cirúrgica e um corredor. No Caso 2 foram analisados a sala cirúrgica, um corredor limpo e um corredor “sujo” (corredor de expurgo); enquanto no Caso 3, a sala cirúrgica, antecâmara e corredor. Os ambientes estudados são hipotéticos. As características construtivas e parâmetros ambientais (temperatura, umidade relativa, velocidade do ar, etc.) foram pré-estabelecidos segundo o tipo de cirurgia, baseando-se em normas brasileiras e algumas internacionais. Os tipos de cirurgias estudadas foram a ortopédica e a abdominal, considerando-as, respectivamente, asséptica e séptica. O conforto térmico foi calculado para os seguintes ocupantes: paciente, cirurgiã, anestesista, enfermeira auxiliar, enfermeira instrumentadora, enfermeira circulante, equipe de preparo e equipe de limpeza, pessoas no corredor e pessoas acessando a antecâmara. A escala utilizada para estabelecer as condições de conforto térmico, foi a ISO 7730. O gasto energético foi simulado para o período de um ano de projeto, enquanto os demais parâmetros, para um dia de verão (21 de janeiro) e um dia de inverno (21 de julho). O software utilizado na simulação foi o Energy Plus, versão 1.03. Com o modelamento foi possível observar o comportamento de cada parâmetro requerido, dentro de um espaço de tempo e nas diferentes regiões brasileiras estudadas. Na simulação, verificou-se que as variáveis, temperatura e umidade relativa, mantiveram-se dentro dos parâmetros exigidos. Estas variáveis, estando sob controle, não expuseram o ambiente a condições favoráveis para a amplificação de microorganismos. O controle de contaminantes nos ambientes, fez-se a partir do diferencial de pressão, da política de acesso de pessoas às salas cirúrgicas, bem como as filtragens recomendadas pelas normas. Com o dimensionamento dos equipamentos, foi possível ter as potências de cada fan-coil no dia de verão e de inverno para cada cidade e tipo de cirurgia. A menor potência encontrada para a sala cirúrgica foi no Caso 2. Dentro das análises realizadas, o layout do Caso 2 se mostrou mais eficiente, do ponto de vista energético, e em relação ao conforto térmico. Em todos os casos o anestesista e o paciente encontraram-se em situação de extremo desconforto, porém, no dia de inverno no Caso 2, apresentaram uma pequena melhora na sensação térmica, enquanto as demais pessoas, mantiveram-se em conforto ou pouco desconfortáveis. Analisando a política de acesso às salas cirúrgicas o layout com dois corredores permite um maior controle da sala cirurgica, diminuindo assim o risco de infecção cruzada nestes ambientes. Com o controle do ambiente interior, melhora-se as condições de segurança e saúde do corpo clínico e pacientes. O uso de simulação computacional mostrou-se uma importante ferramenta de suporte, permitindo avaliar o desempenho de diferentes soluções. A simulação computacional permite identificar ainda na fase de projeto, os projetos que são mais adequados ao uso do ambiente e o de maior qualidade, e os mais eficientes do ponto de vista energético.pt_BR
dc.description.abstractAt the present report, was made a computational simulation of three operating rooms and some adjacent areas. The purpose of this study was to verify the influence of the different layouts in the thermal comfort of the occupants, the indoor air quality, in the HVAC characteristics and in the energy consumption. All the environments were simulated according to the climate conditions of five Brazilian capitals: Belem, Brasilia, Porto Alegre, Recife e Sao Paulo. Three different layouts were studied. In Case 1, the layout consisted of an operating room and a hallway. Case 2 consisted of an operating room, a hallway with ultra-clean air and a second hallway with normal air treatment which is used as exit from the operating room and remove contaminated materials and instruments. Case 3 were considered an operating room, an antechamber and a hallway. The three cases described and studied are hypothetical. The constructive characteristics and the environmental parameters (temperatures, relative humidity, the air velocity, pressure, filters, etc.) were established according to the type of surgery and also based on Brazilian and some International standards. Two types of surgeries were evaluated: the orthopedic and the abdominal, considering them aseptic and septic, respectively. The thermal comfort of the patient, surgical team, support staff and the person, who cleans the operating room, were evaluated. The scale ISO 7730 was used to establish the thermal comfort conditions. The energy consumption was simulated for a one-year project, while the other parameters for one Summer day (21st January) and one Winter day (21st July). The software used in the simulation was the Energy Plus, version 1.03. With the modeling, it was possible to observe the behavior of each required parameters within a time space in the different Brazilian capitals. In the simulation, the environment temperature and the relative humidity were analyzed, and they remained in the demanded parameters. Those variables were under control and, therefore do not exposed the environment to favorable conditions of microorganisms increase. The architectural analysis was made to the politics of people’s access to the operating room. With the equipment dimensioning, it was possible to have the potencies of each fan-coil in the Summer and Winter day for each city and kind of surgery. The lowest power found was the one for the surgery room in Case 2. Based on the results of the simulations, comparing the performance of the three different layouts, Case 2 revealed to be more efficient on the energy consumption and also to the thermal comfort. However, in Case 1, 2 and 3, the anesthesiologist and the patient were in a situation of extreme thermal discomfort, although in winter day Case 2 revealed a small improvement on the feeling of thermal discomfort, while the other people remained in comfort or a little thermal discomfort. Analyzing the politics of people’s access to the operating rooms, Case 2 provides higher control of the indoor environment, since the surgical team and aseptic materials and instruments enter in the operating room for a hallway with clean air and leave the room for another hallway. Case 2 layout works as an architectonic barrier, defining the people behavior in the Operating Unit and, therefore, decreasing the risk of cross-infection. A computational simulation is an important support tool in the performance assessment of architectonic solutions. The use of computational simulation permits to compare and evaluate different design solutions during the design process, and to identify designs that are more efficient, adequate for the use and that provides improved indoor environment quality for the users.en
dc.format.mimetypeapplication/pdf
dc.language.isoporpt_BR
dc.rightsOpen Accessen
dc.subjectSimulação computacionalpt_BR
dc.subjectQualidade do ar interiorpt_BR
dc.subjectConsumo de energiapt_BR
dc.subjectConforto térmicopt_BR
dc.titleEstudo do conforto térmico, do consumo energético e da qualidade do ar interior em salas cirúrgicas, através da simulação computacional e análise de layoutpt_BR
dc.title.alternativeStudy of the thermal comfort, the energy consumption and indoor air quality in operating rooms, through computational simulation and architectural analysis en
dc.typeDissertaçãopt_BR
dc.contributor.advisor-coSiqueira, Luiz Fernando de Góespt_BR
dc.identifier.nrb000883823pt_BR
dc.degree.grantorUniversidade Federal do Rio Grande do Sulpt_BR
dc.degree.departmentEscola de Engenhariapt_BR
dc.degree.programPrograma de Pós-Graduação em Engenharia Mecânicapt_BR
dc.degree.localPorto Alegre, BR-RSpt_BR
dc.degree.date2003pt_BR
dc.degree.levelmestradopt_BR


Thumbnail
   

Este item está licenciado na Creative Commons License

Mostrar registro simples