Show simple item record

dc.contributor.authorFerreira, Carlos Arthurpt_BR
dc.contributor.authorCoser, Elianept_BR
dc.contributor.authorAngelini, Joceli Maria Giacominipt_BR
dc.contributor.authorRossi, José Antonio Donizetept_BR
dc.contributor.authorMartinez, Manuel Luis Barreirapt_BR
dc.date.accessioned2013-07-09T01:51:57Zpt_BR
dc.date.issued2011pt_BR
dc.identifier.issn0104-1428pt_BR
dc.identifier.urihttp://hdl.handle.net/10183/75706pt_BR
dc.description.abstractA study was conducted to evaluate new and laboratory-aged samples of surge arresters and anchorage polymeric insulators, for 12 and 24 kV networks, which are used by the Rio Grande Energia (RGE). Power Utility Polymeric compounds were analyzed by Differential Scanning Calorimetry (DSC), Thermogravimetric Analysis (TG), Dynamic-Mechanic Analysis (DMA), Fourier Transformed Infrared Spectroscopy (FTIR) and Scanning Electronic Microscopy (SEM) to verify changes in the insulator properties due to degradation occurred during the experiments. The analyses were carried out before and after 6 months of aging in laboratory devices (weatherometer, 120 °C, salt spray, immersion in water). After the aging experiments, high-voltage electrical tests were also conducted: a radio interference voltage test and, simultaneously, the total and the internal leakage currents were measured to verify the surface degradation of the polymeric material used in the housing. The impulse current test was applied with current values close to 5, 10 and 30 kA, in order to force an internal degradation. Results showed that only surface degradation is detected at the polymer. The main properties of the parts were not affected by the aging. It confirms that polymer insulator and surge arrestor are appropriate for use in electricity distribution networks.en
dc.format.mimetypeapplication/pdfpt_BR
dc.language.isoengpt_BR
dc.relation.ispartofPolímeros (São Carlos): ciência e tecnologia. São Carlos, SP. Vol. 21, no. 5 (Dec. 2011), p. 436-442pt_BR
dc.rightsOpen Accessen
dc.subjectLinhas de transmissãopt_BR
dc.subjectPolymeric arresteren
dc.subjectSilicone rubber insulatorsen
dc.subjectBorracha de siliconept_BR
dc.subjectSilicone degradationen
dc.subjectIsoladores poliméricospt_BR
dc.subjectMateriais poliméricospt_BR
dc.subjectLeakage currenten
dc.titleEffect of artificial aging on polymeric surge arresters and polymer insulators for electricity distribution networkspt_BR
dc.typeArtigo de periódicopt_BR
dc.identifier.nrb000822978pt_BR
dc.type.originNacionalpt_BR