Avaliação do isolamento sonoro nos quartos do prédio de internação do Hospital de Clínicas de Porto Alegre
View/ Open
Date
2019Author
Advisor
Academic level
Graduation
Title alternative
Evaluation of noise isolation at the hospitalization rooms of Hospital de Clínicas de Porto Alegre
Subject
Abstract in Portuguese (Brasil)
Este trabalho avaliou o nível de pressão sonora produzido por um sistema de refrigeração a ar (air-cooled chillers) posicionado no pátio, nos quartos de internação do Hospital de Clínicas de Porto Alegre. Seguindo determinações das normas NBR 10151/2000 e NBR 10152/1987, foram adquiridos dados nos equipamentos externos e em dois aposentos e foram propostas soluções para reduzir o nível sonoro. Os dados quantitativos, obtidos para duas situações distintas – janelas abertas e fechadas –, revelara ...
Este trabalho avaliou o nível de pressão sonora produzido por um sistema de refrigeração a ar (air-cooled chillers) posicionado no pátio, nos quartos de internação do Hospital de Clínicas de Porto Alegre. Seguindo determinações das normas NBR 10151/2000 e NBR 10152/1987, foram adquiridos dados nos equipamentos externos e em dois aposentos e foram propostas soluções para reduzir o nível sonoro. Os dados quantitativos, obtidos para duas situações distintas – janelas abertas e fechadas –, revelaram que os ambientes não atendem ao estipulado em norma, além de verificar-se falha no estanqueamento das portas. As janelas e portas mostraram-se ineficazes no isolamento sonoro, visto que, mesmo com elas fechadas, o nível de pressão sonora extrapola o limite normativo em até 7,4 dB(A). Como medida de implementação para o controle do ruído, foi proposta a instalação de janelas sobrepostas – instaladas internamente sobre as preexistentes – e a troca das portas por outras, ambas com função isolante. A solução sugerida mostrou-se suficiente para adequar os quartos do bloco de internação aos requisitos para o conforto acústico conforme a norma NBR 10152/1987. ...
Abstract
The present work aims to evaluate the noise level produced by a refrigeration system – air-cooled chillers – located at the courtyard around the hospitalization rooms of Hospital de Clínicas de Porto Alegre. Thus, following the standards of the NBR 10151/2000 and NBR 10152/1987, data was collected from the external equipment and from two rooms, and furthermore solutions for the reduction of the noise level were proposed. The quantitative data, obtained from two different situations – open and c ...
The present work aims to evaluate the noise level produced by a refrigeration system – air-cooled chillers – located at the courtyard around the hospitalization rooms of Hospital de Clínicas de Porto Alegre. Thus, following the standards of the NBR 10151/2000 and NBR 10152/1987, data was collected from the external equipment and from two rooms, and furthermore solutions for the reduction of the noise level were proposed. The quantitative data, obtained from two different situations – open and closed windows –, demonstrated that these environments do not satisfy the standards set in the normative, also showing failures in the sound isolation of the doors. The windows and doors proved to be ineffective at soundproofing, considering that, even when they were closed, the sound pressure level surpassed the normative limit, reaching up to 7.4dB(A). As implementation measures for noise control, it was suggested that secondary windows and new doors could be installed, both with noise isolation properties. The offered solution proved to be enough for adjusting the hospitalization rooms to the requirements for achieving acoustic comfort according to the NBR 10152/1987 normative. ...
Institution
Universidade Federal do Rio Grande do Sul. Escola de Engenharia. Curso de Engenharia Mecânica.
Collections
This item is licensed under a Creative Commons License